The Sumatron Model 100C Demand Controller is designed to accept 3-wire KYZ pulses (form C contact transitions) or 2 wire pulses (form A contact transition) on a single input channel and provide peak fixed and sliding window demand, present demand, and total count on an eight digit LCD display. Additionally, the Model 100C can provide an output relay actuation anytime the demand set point is met or exceeded.

 Engineering units...user selected scaling factors can convert the pulses into engineering units for display. The demand set point can also be selected using engineering units.

Occurrence counter... the number of fixed window intervals that meet or exceed the demand set point will be stored and displayed.

Switch selectable demand intervals...demand intervals from one to ninety minutes are switch selectable in one minute steps.

Switch selectable operation modes...any three of the following four measurements can be selected: total count, present demand, fixed window demand, and sliding window demand.

Switch selectable output relay...one output relay can be switched to provide form C contact transitions that echo the input pulses or a contact transition when the demand set point is met or exceeded.

Synchronizing capability...can be driven by external form C contacts for fixed window demand interval slaving with a master unit.

Backup memory power...the standard design uses a capacitor to provide carry-over power for greater than a four day period.

Bi-color LED's...monitor the state of the pulse input channel and the output relay.

Line frequency time base...the demand interval is derived from the power line frequency.

Switch selectable reset...the peak fixed and sliding window demands and the occurrence counter are reset to zero by coordinating the position of a three position read switch with the operation of the reset push-button.

Smart display...eight digits are provided for the total pulse count and six digits are utilized for the demand readings. When the unit displays demand readings, the eighth or left-most digit will display a letter code to indicate the type of demand under display, i.e., present, fixed or sliding window. The fixed window interval generation, internal or externally slaved, is also indicated on the display.

Diagnostics...three different test routines are provided to ensure proper operation. The unit will verify proper operation of the EPROM program, RAM, and LCD display system.

Surge protected output contacts...RC networks are applied in parallel to output contacts to control the rate of voltage rise across the contacts during circuit opening. The standard design will provide contact protection up to 300 volts and 0 to 100 MA. Where your requirement is greater than 100 MA, please specify the expected load current and voltage and the proper contact protection will be provided at no additional charge.

 

Output Relay Specifications:

  • Mercury wetted form C contacts
  • Bi-stable magnetic latching
  • Billions of operations with proper contact protection (included on circuit board)
  • Contacts limited to 100 VA, 2 amps, or 500 volts peak
  • Maximum operating time of 6 MS

 

Power Requirement:

  • 90-134 VAC
  • Less than 2.5 VA
  • 60 cycles
Testing
Each Demand Controller is energized for 48 hours, followed by a full operational test, to assure service integrity.
 Dimensions
Circuit board - 6 1/4 inches * 4 1/4 inches * 1 1/2 inches
Enclosure options
Warranty
Eighteen Months
 Instruction Manual
A complete instruction manual will be provided with each Model 100 Demand Controller. The manual will cover specifications, theory of operation, application data, parts list and circuit schematic.

Purchase Products | Contact Us!

This site and all contents are Copyright ©2003, Sumatron, Inc. All rights reserved.